Water at the tundish, no hot water, or a cylinder that keeps discharging. We hold both tickets, so the boiler and the cylinder are diagnosed in one visit rather than two.
Answered 24 hours a day by a technical customer service member.
Water at the tundish is never normal, and it is almost never the valve that is dripping. The section below explains what it is actually telling you.
Two details to start. Tell us the make on the cylinder and what you are seeing, and we can usually name the part before we attend.

The London boiler firm that tells you whether it is the boiler or the cylinder before anyone attends. Most heating firms are Gas Safe registered and stop at the appliance. Most plumbers who hold G3 do not touch the boiler. When the hot water goes, that gap is why people pay for two visits to find one fault.

| What we find, in order of frequency | Why it discharges |
|---|---|
| The expansion device has failed | An external vessel has waterlogged, or on a Megaflo the internal air bubble has been absorbed into the water. With nowhere for the expansion to go, pressure rises on every heat cycle and lifts a valve |
| The pressure reducing valve is passing | Or the incoming mains pressure has risen. The working pressure creeps up past what the relief valve will hold |
| The relief valve will not reseat | Debris or scale on the seat. It opened for a good reason once and never closed again |
| The water is genuinely too hot | The thermostat has failed and the cut-out has not. This is the serious one and the valve is doing exactly its job |
Tundish dripping, or hot water gone?
Tell us the make on the label and what you can see. On a cylinder those two answers usually name the part before anybody sets off, which is the difference between one visit and three.| Device | Its job | Typical setting |
|---|---|---|
| Pressure reducing valve | Sets the working pressure of the whole system | Commonly 3 bar |
| Expansion vessel or air bubble | Absorbs the extra volume as water is heated | Pre-charge matched to the pressure reducing valve |
| Thermostat | Controls the stored water temperature | 60 to 65 degrees, and not below 60 |
| High limit cut-out | Cuts the heat if the thermostat fails. Does not reset itself | Around 80 to 85 degrees |
| Expansion relief valve | Lifts on pressure alone. The everyday nuisance valve | Around 6 to 8 bar, depending on the make |
| Temperature and pressure relief valve | The last line of defence, opening on either | Around 90 to 95 degrees or 7 bar, whichever the water reaches first |